PQ3198/6000 KIT - HIOKI Power Quality Analyzer 6000A KIT (PQ3198 W/ 4 X CT7045, 3 X L1021-02, Z4003, 4 X 9804-01, 4 X 9804-02, PQ3100/98 H-CASE-CN)

PQ3198/6000 KIT - HIOKI Power Quality Analyzer 6000A KIT (PQ3198 W/ 4 X CT7045, 3 X L1021-02, Z4003, 4 X 9804-01, 4 X 9804-02, PQ3100/98 H-CASE-CN)
Brand: HIOKI
Product Code: PQ3198/6000 KIT
Availability: In Stock
Specifications: Link to Data Sheet
Video: Link to Video
CAD 14,925.40
Qty: Add to Cart

HIOKI PQ3198/6000 Kit

The HIOKI PQ3198 power quality analyzer records power-system trends and events to investigate voltage dips, swells, interruptions, harmonics and flicker. The four current sensors in each kit are selected for the current range and conductor size shown in the kit contents.

Key Features

  • Measures single-phase and three-phase systems with an additional fourth input channel.
  • Captures transient voltage at 2 MHz sampling and records up to 6 kV peak transients.
  • Tracks power, energy, unbalance, harmonics through the 50th order, interharmonics and 2–80 kHz supraharmonics.
  • Continuous trend and event recording supports investigation of intermittent supply faults.
  • SD storage, LAN and USB communication; PQ ONE software supports analysis and reporting.
  • Current range and accuracy depend on the connected sensors.

Configuration: The current sensors and accessory quantities for this specific kit are listed under Accessories Included. Other sensors and the optional GPS equipment are sold separately. This kit supplies one Z4003 8 GB SD card only. No additional memory card is included.

See Accessories Included for the exact quantities supplied with this configuration.

Contact RCC Electronics for configuration assistance and Canadian application support.

PQ3198 Specifications

Instrument specifications apply under HIOKI's stated measurement conditions. Kit contents are listed separately.

Measurement line type Single-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire or Three-phase 4-wire plus one extra input channel for voltage, current, power measurement (AC or DC measurement)
Voltage ranges Voltage measurement: 600.00 V rms
Transient measurement 6.0000 kV peak
Current ranges 500.00 mA to 5.0000 kA AC (depends on current sensor in use)
Power ranges 300.00 W to 3.0000 MW (determined automatically based on voltage and current range in use)
Basic accuracy Voltage: ±0.1% of nominal voltage
Current: ±0.1 % rdg. ±0.1 % f.s. + current sensor accuracy
Active power: ±0.2 % rdg. ±0.1 % f.s. + current sensor accuracy
Measurement items 1. Transient voltage : 2 MHz sampling
2. Frequency cycle : Calculated as one cycle, 40 to 70 Hz
3. Voltage (1/2) RMS: one cycle calculation refreshed every half cycle
Current (1/2) RMS: half-cycle calculation
4. Voltage swell, Voltage dips, Voltage interruption
5. Inrush current
6. Voltage waveform comparison
7. Instantaneous flicker value: As per IEC61000-4-15
8. 200 ms frequency: Calculated as 10 or 12 cycles,40 to 70 Hz
9. 10 sec frequency: Calculated as the whole-cycle time during the specified 10 s period, 40 to 70 Hz
10. Voltage waveform peak, Current waveform peak
11. Voltage, Current, Active power, Apparent power, Reactive power, Active energy, Reactive energy, Power factor, Displacement power factor, Voltage unbalance factor, Current unbalance factor, and efficiency
12. High-order harmonic* component (voltage/ current): 2 kHz to 80 kHz
*Supraharmonic
13. Harmonic/ Harmonic phase angle (voltage/ current), Harmonic power: 0th to 50 th orders
14. Harmonic voltage-current phase angle: 1th to 50 th orders
15. Total harmonic distortion factor (voltage/ current)
16. Inter harmonic (voltage/ current): 0.5 th to 49.5 th order
17. K Factor (multiplication factor)
18. IEC Flicker, Δ V10 Flicker
19. Mains signaling voltage
Record Repeated ON: 1 year, Maximum recording event: 9999 × 366 days (up to 9999 events per day)
Repeated off: 35 days, maximum recording event: 9999 events
Interfaces SD/SDHC memory card, LAN (HTTP server function / FTP function), USB2.0 (for communication)
Display 6.5-inch TFT color LCD (640 × 480 dots)
Power supply AC adapter Z1002 (100 V to 240 V AC, 50/60 Hz, rated current 1.7 A), Battery Pack Z1003 (Continuous use: 180 minutes, Charging time: Max. 5 hr 30 m with AC adapter)
Dimensions and mass 300 mm (11.81 in)W × 211 mm (8.31 in)H × 68 mm (2.68 in)D, 2.6 kg (91.7 oz) (including Battery Pack Z1003)

HIOKI official specifications and accessories

PQ3198/6000 Kit Contents

The following quantities describe this kit configuration.

Qty Model Included item
1 PQ3198 power quality analyzer
4 CT7045 AC flexible current sensor, 600 A / 6000 A, 180 mm loop diameter
3 L1021-02 Branch connection cord, black
1 Z4003 8 GB SD memory card
4 9804-01 Magnetic adapter, red
4 9804-02 Magnetic adapter, black
1 PQ3100/98 H-CASE-CN Hard carrying case (Canadian kit configuration)

Standard Accessories Supplied with the Instrument

These are supplied with the main instrument. Items already counted in the kit table are not repeated.

Qty Model Included item
1 L1000 Voltage cord set: red, yellow, blue and grey leads (one each), four black leads and eight alligator clips; 3 m
20 — Spiral tube
— — Colour clips
1 Z1002 AC adapter
1 Z1003 Rechargeable battery pack
1 — Strap
1 — USB cable, 1 m
1 — Instruction manual
1 — Measurement guide

Included versus optional: The current sensors and accessory quantities for this specific kit are listed under Accessories Included. Other sensors and the optional GPS equipment are sold separately. This kit supplies one Z4003 8 GB SD card only. No additional memory card is included.

HIOKI official specifications and accessories