Short answer: IEEE 2962-2025 provides recommended practices for stationary lithium-ion batteries across installation, operation, maintenance, testing and replacement. A meaningful capacity test considers the complete battery system, including the battery management system (BMS), operating limits and the specified duty. Test equipment and procedures must be matched to the battery manufacturer's instructions.
Stationary lithium-ion batteries are increasingly used in backup power and energy-storage systems. Whether the application is a UPS, telecommunications site or industrial facility, battery capacity is only useful if the system can deliver the required power when called upon.
IEEE 2962-2025 addresses the lifecycle of stationary lithium-ion batteries. It was approved in November 2025 and published on March 25, 2026. It is a recommended practice; the project requirements, manufacturer instructions and applicable safety rules remain essential to an actual test plan.
IEEE describes guidance covering system design, storage, installation, ventilation, instrumentation, operation, maintenance, capacity testing and replacement. Its scope includes stationary standby and cycling applications, while noting that some recommendations may be excessive for smaller residential systems.
IEEE 2962 is specific to lithium-ion stationary applications. Other established IEEE recommended practices address different chemistries: IEEE 450 covers vented lead-acid, IEEE 1188 covers valve-regulated lead-acid and IEEE 1106 covers vented nickel-cadmium batteries. Select the applicable document and edition for the installed system.
| Planning question | What to review | Why it matters |
|---|---|---|
| Is the system ready? | Manufacturer guidance, state of charge, alarms and approved test conditions | A baseline and safe starting condition support meaningful results. |
| Can it deliver the duty? | Required discharge profile, endpoint, battery and BMS limits | Capacity and the system's ability to sustain the specified duty must both be considered. |
| What should be recorded? | Total voltage, current, time, temperature and accessible module or cell data | A traceable record helps interpret deviations and compare future tests. |
A lithium-ion battery system relies on a BMS to monitor cells and temperatures and to manage protective functions. DV Power emphasizes that the battery and its BMS must be considered together: a protective disconnection before the defined test endpoint can prevent the system from delivering the specified duty, even if a capacity value appears acceptable.
Do not defeat, bypass or alter protective functions to complete a test. Document any alarm or disconnection, stop according to the approved procedure, and investigate with the battery manufacturer or system owner. Interpretation depends on the actual test method and acceptance criteria.
DV Power identifies acceptance, performance, service and modified-performance tests in its discussion of IEEE 2962. Each begins with a different purpose: confirming the installed system, tracking capability over time or checking performance against a defined service duty. The authorized test procedure should define load profile, duration, endpoints, temperatures, data collection and acceptance criteria.
Before testing, review the battery's manufacturer-approved state-of-charge and commissioning instructions, the BMS status, environmental conditions, backup arrangements and operating permissions. Avoid applying a generic storage charge percentage or voltage to every lithium chemistry and system.
Maintenance extends beyond the modules themselves. Review accessible battery and BMS status, alarms, temperature sensing, balancing information and records, together with cooling, cleanliness and site safety systems as applicable. Record the observations and follow the system manufacturer's maintenance schedule and corrective-action process.
DV Power also discusses round-trip-efficiency testing and an optional charge test. These answer different questions from a discharge capacity test; establish the measurement boundary and method before comparing results.
The DV Power battery-testing range includes BLU load units for controlled battery discharge. DV Power describes the BLU-C series as suitable for capacity testing battery strings including lithium-ion, with configuration-dependent voltage, current and power capabilities. Its BVS or BVS-4 monitoring options can support voltage monitoring with compatible systems.
The BLU-T series is another option for suitable lower-voltage battery systems. Select the exact load unit and monitoring hardware for the battery's voltage throughout discharge, required current or power, duty duration, BMS limits, connections and site conditions. A product's ability to perform a discharge does not by itself establish that a complete test complies with IEEE 2962.
Replacement decisions should follow the battery manufacturer's requirements, the system's safety and service duty, the owner's documented criteria and the applicable standard. Capacity is one input; BMS condition, alarms, cell behaviour, reliability and operating history also matter. DV Power notes that the end-of-life decision is not necessarily a single universal percentage for every system. Confirm any numerical criteria directly in the applicable IEEE document and manufacturer instructions.
RCC Electronics can help Canadian utilities, data centres, telecommunications operators and service teams review a DV Power configuration. Provide the battery chemistry, voltage range, required discharge duty, duration, available monitoring points, BMS restrictions and test-site requirements. Confirm the final load unit, cables, monitoring system, safety plan and backup arrangements before scheduling the test.
What is the full standard designation?
IEEE 2962-2025. IEEE lists it as an active recommended practice published on March 25, 2026.
Does it cover only capacity testing?
No. IEEE describes recommendations across design, storage, installation, operation, maintenance, testing and replacement.
Why record BMS events?
Alarms, limits or a protective disconnection may explain why a system did not complete its intended duty. Record and interpret them under the approved procedure.
Can one tester be used on every lithium-ion battery?
No. Voltage range, discharge current, power, duration, connection method and manufacturer restrictions must match the system.
Does using a BLU automatically make a test IEEE compliant?
No. Compliance depends on the complete procedure, configuration, conditions and interpretation as well as the instrument.
IEEE 2962-2025 official publication and scope · DV Power overview of IEEE 2962 · DV Power capacity testing and BVS monitoring.
RCC Electronics can help review the DV Power equipment and monitoring configuration for your battery system.