Short answer: IEC 61000-4-30 defines methods for repeatable power-quality measurements. Its evolution from the 2003 first edition to the 2025 fourth edition changed measurement methods and classes. HIOKI's PQ3198A is specified to Edition 4 Class A, while PQ3198 and PQ3100 are specified to Edition 3 Class A and Class S respectively.
Power-quality studies depend on measurements that different engineers and instruments can compare. Voltage dips, interruptions, harmonics and other phenomena must be measured consistently before a team can investigate an event or evaluate a supply against a separate performance requirement.
IEC 61000-4-30 addresses measurement methods, not a universal pass/fail limit for every facility. This guide follows the published editions and maps selected HIOKI analyzers to the edition and class supported by available manufacturer evidence. It is current to November 19, 2026.
| Edition | Publication | Development |
|---|---|---|
| 1 | 2003; corrigendum 2006 | Established standardized in-situ power-quality measurement methods. |
| 2 | 2008 | Clarified Class A and B methods and introduced Class S for surveys. |
| 3 | 2015; corrigendum 2016; amendment 2021 | Added rapid voltage change, made current measurement normative, and clarified Class A and S. Class B moved to an informative annex. |
| 4 | 2025; corrigendum 2026 | Updated voltage-event and rapid-voltage-change methods; revised conducted-emission annexes and removed the Class B annex. |
The 2021 amendment produced the consolidated Edition 3.1; it was not Edition 4. IEC published Edition 4 in October 2025 and issued a corrigendum in July 2026. Check the edition specified in your project or contract.
IEC incorporated the third-edition amendment and corrigendum, corrected and extended rapid-voltage-change methods, and updated voltage-event methods. It separated guidance for conducted emissions from 2 kHz to 9 kHz and added a method for 9 kHz to 150 kHz in a new annex. These annexes should not be treated as proof that every instrument measures every frequency range or parameter.
The fourth edition covers Class A and Class S measurement methods for in-situ measurements on AC systems with a declared 50 or 60 Hz fundamental frequency. Instrument capabilities outside that scope do not automatically carry the same standard claim.
IEC identifies A as advanced and S as surveys. Class A specifies more demanding measurement requirements for applications needing consistent, comparable results; Class S serves survey applications. Choose the class from the applicable project specification and measurement objective, not simply the label on the instrument.
IEC 61000-4-30 describes measurement methods; IEC 62586-2 addresses verification of instrument compliance. Other documents, such as EN 50160 or IEEE 519, address different evaluation contexts and should not be treated as interchangeable with the measurement-method standard.
| HIOKI model | Documented IEC 61000-4-30 alignment | Selection note |
|---|---|---|
| PQ3198A | Edition 4 (2025), Class A | HIOKI's November 2026 announcement identifies the new model as Ed. 4 Class A. Contact RCCE for its exact configuration and availability. |
| PQ3198 | Edition 3, Class A | HIOKI identifies the applicable update to version 2.00 for Ed. 3 Class A. Verify the individual unit's firmware and documentation. |
| PQ3100 | Edition 3, Class S | HIOKI lists this survey-class instrument as Ed. 3 Class S. Confirm current product status and the project requirement. |
| PW3198 | Edition 2, Class A | Discontinued legacy model. Check the installed instrument's documentation before relying on historical results. |
Class and edition are separate attributes. A Class A label by itself does not establish Edition 4 compliance. PQ3198 and PQ3198A are different products; do not assume an update converts one into the other.
HIOKI states that PQ3198A records event waveforms of up to 11.2 seconds and samples transient voltage at 2 MS/s, up to ±6 kV peak under the stated conditions. It has four voltage and four current channels, with the fourth voltage channel isolated from the first three for suitable AC/DC applications.
Distinguish ratings: its 1000 V CAT III / 600 V CAT IV safety category is not the continuous RMS measurement range. HIOKI stated a maximum 600 V RMS range at launch. Confirm the latest manufacturer documentation, leads and sensors before use.
Define the required edition, class, phenomena, recording duration, wiring and current range before choosing a system. Review certificates, firmware, time synchronization, calibration, leads and current sensors as a complete measurement chain. Qualified personnel should follow site electrical safety procedures.
RCC Electronics can help Canadian utilities, data centres, industrial facilities and service teams review configuration and availability. HIOKI's November 2026 announcement scheduled first PQ3198A shipments for late February 2027; confirm current Canadian availability and pricing with RCCE. The PQ3198A does not yet have a verified individual RCCE product listing.
Is Edition 4 the latest edition?
As of November 19, 2026, IEC lists the 2025 fourth edition with a 2026 corrigendum as valid.
Does Class A automatically mean Edition 4?
No. Identify the edition and the exact model and firmware in the manufacturer's evidence.
Does the PQ3198A meet Edition 4 Class A?
Yes. HIOKI's November 2026 launch announcement explicitly states IEC 61000-4-30:2025 Ed. 4 Class A compliance.
Does a PQ3198 meet Edition 4?
The HIOKI material cited here identifies PQ3198 as Edition 3 Class A with the applicable update; it does not establish Edition 4 compliance.
Does the standard set all pass/fail limits?
No. It defines measurement methods; determine the applicable limits or assessment criteria separately.
IEC 61000-4-30:2025 publication and edition history · IEC 2008 edition · IEC 2015 edition changes · HIOKI PQ3198A launch announcement · HIOKI power quality analyzers · HIOKI PQ ONE update history · HIOKI PW3198 brochure.
RCC Electronics can help review the required standard, instrument, sensors and accessories.
* This overview is not a substitute for the applicable standard, instrument certificate or current manufacturer documentation. Verify the required edition, firmware, configuration, safety limits and availability.